Project Overview

Ice Rink Chiller Industry and application. An indoor ice rink operated by a leisure and sports company inside a shopping mall. The rink is a 30 × 15 m sheet (450 m²) with 30 mm of ice over a concrete pad, cooled through a polyethylene brine grid cast into the slab. Public sessions run seven days a week, with figure skating and junior hockey training in the early mornings.

Pain points. The rink was running on a used air-cooled chiller inherited from the previous tenant, and the operation had settled into a routine of workarounds:

Project location. Southeast Asia, tropical climate, 32 to 35 °C ambient year-round with high humidity.

Requirements

Our Solution

Unit selected. A water-cooled low-temperature glycol chiller, nominal 62 kW at −11 °C leaving brine and 35 °C condensing water inlet. Two scroll compressors, 30 kW installed compressor power, staged loading.

Configuration.

Why this configuration, against the specific pain points.

Unclear performance was answered by writing the capacity, the brine temperature and the condenser water temperature onto the commissioning sheet, at site conditions.

Key Technical Parameters

ItemSpecification
Nominal cooling capacity62 kW at −11 °C leaving brine, 35 °C condensing water inlet
Compressors2 × scroll, staged, 30 kW total input
RefrigerantR404A
Leaving brine temperature−11 °C, adjustable −15 to −5 °C
Secondary refrigerant30 % propylene glycol
Brine flow18 m³/h at 3 K temperature rise
Evaporatorstainless steel plate, low-temperature design
Condensershell-and-tube, cooling tower loop, 35 / 40 °C
Buffer tank500 L, insulated
Temperature stability±0.5 K at outlet header, steady load
ControlPLC, remote alarm, local HMI
Power supply380 V / 50 Hz / 3 phase
Protectionantifreeze, flow switch, high/low pressure, phase sequence

Figures above are the project setpoints and reference values at the stated conditions. Site measurements are taken at the outlet header, not at the rink grid.

Project Photos

Results & Benefits

Testimonial

“The ice finally behaves the same on a Sunday afternoon as it does on a Tuesday morning. Resurfacing water freezes before the next group comes on, and we have not had a high-pressure trip since the unit went in.”

— Facility Manager, ice rink operator

CTA

Share your cooling requirement with us, we provide customized chiller solution.

Three items still need action before this goes live: the photo slots must be filled with the real project photographs (the three files above are diagrams and scene renders, not site photos), the model code has to be inserted from the order, and the figures in Results & Benefits have to be checked against the commissioning report and the customer’s electricity log.